Basic Info.
Product Description
Description
Winner control ball valve consists of WVA4-… series rotary actuator and WUPBV… series ball valve. Equal percentage flow characteristic guarantees the valve performances of stability.
Application
Winner motorized Control ball valves are widely used in HVAC system, heating system, water treatment equipment, and water running control in industrial automation, such as: AHU, flesh air-handling unit, differential pressure control unit and heat exchanger for flow regulation and on/off control.
Operational mode of Motorized Water Valve
Winner motorized control ball valve is motor-operated by a type of WVA4-1…, WVA4-2…, and WVA4-3… actuator. The actuator is controlled by a modulating on/off , 3-point or proportional control system and move the ball of the valve, to the opening position dictated by the control signal.
Technical data:
Valve body
Medium: cold/hot water, with 50% glycol Temperature of medium: 2...90 Centigrade
Rated pressure: PN16 Pipe connector: internal thread
Ambient temp. range: -5...+60 Centigrade ;0...90%RH
Valve type: 2-way
Material
Valve body: U-PVC, C-PVC, PP Stem: U-PVC, C-PVC, PP
Stem O-Ring: EPDM, FPM Ball: U-PVC, C-PVC, PP
Carrier O-Ring: EPDM, FPM Union: U-PVC, C-PVC, PP
End Connector: U-PVC, C-PVC, PP End Connestor O-Ring: EPDm, FPM
Dampener Seal: EPDM, FPM Mounting Clamp: PVC-M, SUS304
Bolt: SUS304
Model No. | Type | DN(mm) | Inch | Kvs(m3/h) | Pmax(KPa) | Ps(KPa) |
WUPBV215 | 2-way | DN15 | 1/2" | 6.15 | 1000 | 1400 |
WUPBV220 | DN20 | 3/4" | 10.5 | 1000 | 1400 | |
WUPBV225 | DN25 | 1" | 16.1 | 1000 | 1400 | |
WUPBV232 | DN32 | 1 1/4" | 16 | 1000 | 1400 | |
WUPBV240 | DN40 | 1 1/2" | 25 | 1000 | 1400 | |
WUPBV250 | DN50 | 2'' | 43 | 1000 | 1400 |
Actuator
WVA4-106 AC220V, 3-Point
Output torque: 6 N.m Angle of rotation: 90°
Protect rank: IP54 On/off time: 50-90S
Manual handle Automatic overload protection system
Manual selection of ball rotation direction: C.W. /C.C.W, factory setting is C.W.
Brown wire is power on counterclockwise rotation, valve open
Red wire is power on clockwise rotation, valve close
Brown or red wire is power off Valve keep the current position
Model No. | Working Voltage | Actuator type | Output torque | Consumption | Valve body |
WVA4-106 | 220VAC | 3-point | 6N.m | 6VA | WUPBV215 WUPBV220 WUPBV225 WUPBV232 WUPBV240 WUPBV250 |